+39 030 320 301 [email protected]

DETUNED HARMONIC REACTORS

Harmonics progressively shorten the operating life of capacitors

 

Harmonics are an increasing problem in our networks. In fact, they are responsible for the reduction of the lifespan of capacitors, for circuit feedbacks, high THDi currents and other issues.
Most harmonics are generated by the use of several power electronic devices and non-linear devices such as inverters, UPS, variable frequency drives (VFDs), arc furnaces, florescent lights, computers, etc.

Gruppo Energia detuned reactors (line reactors) are designed to protect capacitors, by preventing the amplification of harmonic currents.

Moreover, line reactors connected with capacitors create a resonance frequency circuit which has a specific tuning frequency. This allows the filtration of harmonic currents and reduces the distortion level of the network.

The most common reactor tuning frequencies are:

  • 189 Hz (P = 7%) which mitigates the 5th (and higher) harmonic order;
  • 134 Hz (P = 14%) which mitigates the 3rd harmonic order (and higher orders). 

 

Benefits of using Gruppo Energia harmonic reactors:

Capacitors will last you longer
Save money by reducing THDi (total current harmonic distortion)
Protect your network from circuit feedback
Save money by reducing the reactive power consumption
Reduce losses at the line transformer and in neutral wire load
Protect your system from interference

Get premium quality for a competitive price!

Too good to be true? Contact us today for a quote.

 

Standards:

  • DIN EN 61558-1 (VDE 0570-1): 2016-06; EN 61558-1:2016
  • DIN EN 61558-1 (VDE 0570-1): 2006-07; EN 61558-1:2006

Origin: 100% made in Italy

FEATURES

GE-RTM3 (adjusted rating)

GE-RT3 (non-adjusted rating)

detuned harmonic reactor Gruppo Energia

For more information, please consult the table below: 

Voltage range 220 V to 1000 V
Frequency 50 Hz / 60 Hz
Relative impedance 5,67%
Tuning frequency 210 Hz / 250 Hz
Power range 1 kVar to 200 kVar
Insulation class Class H (other classes available upon request)
Winding material Al (Cu upon request)
Temperature class Class F (other classes available upon request)
Protection rating IP 00
Test voltage 3kV/1′
Maximum ambient temperature Ta 40° C (50°C or higher upon request)

Other configurations are available upon request. For more information, don’t hesitate to contact us.

 

GE-RTM3 (adjusted rating)

GE-RT3 (non-adjusted rating)

detuned harmonic reactor Gruppo Energia

For more information, please consult the table below: 

Voltage range 220 V to 1000 V
Frequency 50 Hz / 60 Hz
Relative impedance 7%
Tuning frequency 189 Hz / 230 Hz
Power range 1 kVar to 200 kVar
Insulation class Class H (other classes available upon request)
Winding material Al (Cu upon request)
Temperature class Class F (other classes available upon request)
Protection rating IP00
Test voltage 3kV/1′
Maximum ambient temperature Ta 40° C (50°C or higher upon request)

Other power and voltage levels are available upon request. For more information, don’t hesitate to contact us.

GE-RTM3 (adjusted rating)

GE-RT3 (non-adjusted rating)

detuned harmonic reactor Gruppo Energia

For more information, please consult the table below: 

Voltage range 220 V to 1000 V
Frequency 50 Hz / 60 Hz
Relative impedance 14%
Tuning frequency 134 Hz / 160 Hz
Power range 1 kVar to 200 kVar
Insulation class Class H (other classes available upon request)
Winding material Al (Cu upon request)
Temperature class Class F (other classes available upon request)
Protection rating IP00
Test voltage 3kV/1′
Maximum ambient temperature Ta 40° C (50°C or higher upon request)

Other power and voltage levels are available upon request. For more information, don’t hesitate to contact us.

Share to