LOW VOLTAGE CAPACITORS

What if you never had to wait for months anymore in order to get your capacitors?

Our delivery time starts from 2 weeks*!

 

Main features of Gruppo Energia capacitors for Low Voltage applications:

fully customizable  to suit your needs;

dry type;

– high quality (we are certified CE, VDE, UL, cULus, ISO, SASO, EAC);

 

Need assistance? 

Do you need help in choosing the right capacitors for your needs? Contact us! Our technical department is always happy to help!

Alternatively, you can read our suggestions here

 

*for certain products and depending on the season. 

 

Standards:

  • DIN EN 60831-1 (VDE 0560-46): 2014-11; EN 60831-1:2014
  • DIN EN 60831-2 (VDE 0560-47): 2014-11; EN 60831-2:2014

Origin: 100% made in Italy

 

OUR SERIES

four capacitors aluminium case

RCM-INB-3

Three-phase power factor correction capacitors

Designed to be used in standard conditions, where the presence of non-linear loads is not significant.

NLL < 10%

Applications: 

  • Networks with non significant non-linear loads;
  • Standard overcurrent;
  • Standard operating temperature;
  • Normal switching frequency;
  • Standard life expectancy.

For more information, please consult the table below: 

General
Voltage range 220 V to 780 V
Frequency 50 Hz / 60 Hz
Power range 1 kVar to 62,5 kVar
Insulation level 3/8 kV
Dielectric Al/Zn metallized polypropylene film
Operating conditions
Ambient temperature min. -25°C / max. 55° C
Overvoltage Un +10% for 8 hrs. daily
Overcurrent up to 1,5 x In (Including Harmonics)
Inrush current up to 180 x In
Service life up to 100.000 hrs.
Harmonic presence NLL <10%

Other power and voltage levels are available upon request. For more information, don’t hesitate to contact us.

 

 

RCM-INP-3

Three-phase power factor correction capacitors (heavy duty)

Resistant to current overloads and designed to work in difficult conditions, even in case of a limited quantity of non-linear loads. The current resistance of the Intact Plus series is higher compared to the previous capacitor series.

NLL < 20%

Applications: 

  • Few non-linear loads;
  • Significant overcurrent;
  • High operating temperature;
  • Significant switching frequency;
  • Long life expectancy.

Please consult the table below: 

 

General
Voltage range 220 V to 550 V
Frequency 50 Hz / 60 Hz
Power range 2,5 kVar to 50 kVar
Insulation level 3/8 kV
Operating conditions
Ambient temperature min. -45°C / max. 60° C
Overvoltage Un +10% for 8 hrs. daily
Overcurrent up to 1,8 x In (Including Harmonics)
Inrush current up to 250 x In
Service life up to 160.000 hrs.
Harmonic presence NLL <20%

 

Other power and voltage levels are available upon request. For more information, don’t hesitate to contact us.

 LV three phase capacitors for power factor correction. Gruppo Energia

 

RCM-INA-3

Three-phase power factor correction capacitors (extra heavy duty)

Highly reliable capacitors for operation in harsh environments or when there is a significant level of non-linear loads. They are resistant to high overloads in current and voltage. Intact AllPower series is also resistant to high temperatures.

NLL <25%

Applications: 

  • Significant number of non-linear loads (up to 25%);
  • Significant overcurrent;
  • Extreme temperature conditions;
  • Significant switching frequency;
  • Extra long life expectancy.

For more information, please consult the table below: 

General
Voltage range 220 V to 550 V
Frequency 50 Hz / 60 Hz
Power range 2,5 kVar to 30 kVar
Insulation level 3/8 kV
Operating conditions
Ambient temperature min. -45°C / max. 60° C
Overvoltage Un +10% continuous operation
Overcurrent up to 2,5 x In (Including Harmonics)
Inrush current up to 280 x In
Service life up to 180.000 hrs.
Harmonic presence NLL < 25%

 

Other power and voltage levels are available upon request. For more information, don’t hesitate to contact us.

four capacitors aluminium case

RCM-INR-3

Three-phase power factor correction capacitors

Designed for being used with detuned harmonic reactors. This is the optimal solution for compensating reactive power in networks featured by a significant quantity of non-linear loads, where the use of reactors is essential.

NLL <30%

Applications: 

  • Very high level of non-linear loads (up to 30%);
  • Significant overcurrent;
  • Standard operating temperature;
  • Significant switching frequency;
  • Long life expectancy.

For more information, please consult the table below: 

General
Voltage range 220 V to 780 V
Frequency 50 Hz / 60 Hz
Power range 2,5 kVar to 50 kVar
Insulation level 3/8 kV
Operating conditions
Ambient temperature min. -45°C / max. 55° C
Overvoltage Un +10% continuous operation
Overcurrent up to 1,8 x In (Including Harmonics)
Inrush current up to 250 x In
Service life up to 160.000 hrs.
Harmonic presence NLL < 30%

 

Other power and voltage levels are available upon request. For more information, don’t hesitate to contact us.

Single Phase Capacitors Gruppo Energia

RCM-1:

Single-phase capacitors designed to be used in standard conditions, where the presence of non-linear loads is not significant.

NLL < 10%

Applications: 

  • Networks with non significant non-linear loads;
  • Standard overcurrent;
  • Standard operating temperature;
  • Normal switching frequency;
  • Standard life expectancy.

For more information, please consult the table below: 

General
Voltage range 220 V to 1000 V
Frequency 50 Hz / 60 Hz
Power range 0,25 kVar to 50 kVar
Insulation level 3/8 kV
Operating conditions
Ambient temperature min. -40°C / max. 55° C
Overvoltage Un +10% for 8 hrs. daily
Overcurrent up to 1,5 x In (Including Harmonics)
Inrush current up to 180 x In
Service life up to 100.000 hrs.
Harmonic presence NLL <10%

Other power and voltage levels are available upon request. For more information, don’t hesitate to contact us.